C & I Air-cooling Cabinet Parameters

Model No. INEP5-125kW/215kWh
Grid/DG side parameters
Rated power 125kW
Maximum output power 137kW
Grid voltage 400V AC
Frequency range 50~60Hz
Rated AC current 180A @ 45°C
Can it operate off grid Yes
Other parameters
Grid connection type 3W+PE or 3W+N+PE
Off-grid conversion 20ms
Diesel engine starting mode I/O
Topological mode DC_Bus
PCS peak efficiency 99.73%
Overload capacity 110%, 1min; 120%, 10s
Fire fighting system Perfluorohexane/Aerosol
Battery system
System energy 215.04kWh
Battery type LFP-280Ah
Nominal voltage 768V
Operating voltage range 672V~864V
Max charge and discharge current 140A
PV system
Maximum input power 110kW
Maximum input current 300A
MPPT channels 4
MPPT power per channel/maximum power 30kW/35kW
Start-up voltage/Tracking voltage range DC 200V/DC 250V~650V
System Parameters
Cooling method Forced air cooling
Noise/Protection level <65dB/PS4
Operating humidity/Operating temperature 0-95% (no condensation)/-20°C~+60°C
Human-machine interface HMI/Cloud Platform
Installation method Outdoor-cabinet
Overall weight ≤2800kg
Dimension (WDH) 160012002200mm
Communication method RS485, CAN, Ethernet, dry contact
Altitude 4000m,<2000m Power reduced
Battery product certification IEC 62619, IEC 63056, IEC 60730, IEC/EN 61000, IEC 62477
PCS certification standards IEC 62477-1 & IEC 61000-6-2, VDE-AR-N 4105, NRS 097-21-1: 2017, GB/T34126-2017, GB/T34133-2017
Full container certification UN38.3

 

Off Grid Switching Cabinet Parameters

Model No. 2 parallel machines 5 parallel machines
Grid--DG side parameters
Rated power 250kW 625kW
Maximum output power 274kW 685kW
Grid voltage 400V AC 400V AC
Frequency range 50~60Hz 50~60Hz
Rated AC current 360A @ 45°C 900A @ 45°C
Other parameters
Grid connection type 3W+N+PE 3W+N+PE
Diesel engine starting mode I/O I/O
Overload capacity 110%, 1min; 120%, 10s 110%, 1min; 120%, 10s
STS parameters
Rated power 500kW 1250kW
Nominal voltage AC400V AC400V
Frequency range 50~60Hz 50~60Hz
Off-grid conversion 20ms 20ms
Switching device Thyristor Thyristor
Load side parameters
Rated power 250kW 625kW
Maximum output power 274kW 685kW
Grid voltage 400V AC 400V AC
Frequency range 50~60Hz 50~60Hz
Rated AC current 360A @ 45°C 900A @ 45°C
System Parameters
Cooling method Forced air cooling Forced air cooling
Noise/Protection level <65dB/PS4 <65dB/PS4
Operating humidity/Operating temperature 0-95% (no condensation)/-20°C~+60°C 0-95% (no condensation)/-20°C~+60°C
Human-machine interface HMI/Cloud Platform HMI/Cloud Platform
Installation method Outdoor-cabinet Outdoor-cabinet
Communication method RS485, CAN, Ethernet, dry contact RS485, CAN, Ethernet, dry contact
Altitude 4000m,<2000m Power reduced 4000m,<2000m P

 

Note: This specification is only suitable for Vietnam Market.

HEISSE TAGS :
Eine Nachricht hinterlassen
Sollten Sie Interesse an uns haben und weitere Einzelheiten erfahren möchten, hinterlassen Sie bitte hier eine Nachricht, wir werden uns so schnell wie möglich bei Ihnen melden!
einreichen

Verwandte Produkte

C & I Air-cooling Cabinet
C & I Air-cooling Cabinet
  MEHR +

Melden Sie sich für exklusive Angebote und Updates an!

KONTAKTIERE UNS
Support-Hotline :+86 0592 2263666
Kontakt E-mail:sales@chinacnd.com
Firmenanschrift :19F, C&D International Building, No.1699 Huandao East Road, Siming District, Xiamen City, Fujian Province, China
© Xiamen C&D Emerging Energy Co., Ltd. Alle Rechte vorbehalten . Seitenverzeichnis | Blog | XML | Datenschutzrichtlinie

heim

Produkte

Kontakt